Speci caties
380-480 V, behuizingsgrootte A, B en C
Behuizing
Vermogen [kW]
A2
A3
A4
A5
B1
B2
B3
B4
7
7
C1
C2
C3
C4
Tabel 7.20 380-480 V, behuizingsgrootte A, B en C
164
VLT
Aanbevolen
zekeringgrootte
1,1-4,0
gG-10 (0,37-3)
gG-16 (4)
5,5-7,5
gG-16
1,1-4,0
gG-10 (0,37-3)
gG-16 (4)
1,1-7,5
gG-10 (0,37-3)
gG-16 (4-7,5)
11-18,5
gG-40
22–30
gG-50 (18,5)
gG-63 (22)
11–18
gG-40
22–37
gG-50 (18,5)
gG-63 (22)
gG-80 (30)
37–55
gG-80 (30)
gG-100 (37)
gG-160 (45)
75–90
aR-200 (55)
aR-250 (75)
45–55
gG-100 (37)
gG-160 (45)
75–90
aR-200 (55)
aR-250 (75)
Danfoss A/S © 09/2014 Alle rechten voorbehouden.
®
AQUA Drive FC 202
Aanbevolen
maximale zekering
gG-25
gG-32
gG-32
gG-32
gG-80
gG-100
gG-63
gG-125
gG-160
aR-250
gG-150 (37)
gG-160 (45)
aR-250
Aanbevolen circuit-
Maximaal uitschakel-
breaker
niveau [A]
Moeller
PKZM0-25
PKZM0-25
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
100
PKZM4-50
NZMB1-A100
100
NZMB2-A200
160
NZMB2-A250
250
NZMB2-A200
150
NZMB2-A250
250
25
25
25
25
63
50
MG20N610