All models are fitted with a connection box with cable glands & terminals and 5m cable
•
Follow the instructions as stated under the previous heading 'General'.
•
Ensure that the cable gland fits the individual cable used with respect to clamping size
and type of cable. If not then apply a suitable cable gland and make sure that it is
approved for its application.
•
Connect an external earth wire to the external earth boss and ensure that this is
sufficiently connected to electrical ground.
•
The electrical power supply must be connected to the supplied power cable
•
For connection the cable use an electrical isolating switch or a junction box which is
explosion-safe in accordance with the classification of its environment.
8.
Opening of the housing
The unit contains no components that need direct access in normal operation. The following
warning is marked: "The air conditioning unit is modified to explosion-safe meeting ATEX
requirements II 3 G. No serviceable parts inside. Refer to qualified personnel as substitution
of parts may impair the suitability for use in hazardous areas."
The housing may only be opened under non-hazardous safe conditions. To do this follow the
instructions as described under the following heading 'Repair'.
9.
Maintenance
For the maintenance of the AR-054 air conditioning units the requirements as stated in
EN 60079-17 apply.
If the air conditioning unit and the connection cable are no longer in good condition or are
very dirty or damaged they must be repaired or cleaned immediately.
The power supply to the air conditioning units must be switched off and may only be restored
after the maintenance has been carried out and approved.
For the advised maintenance cycles of the air conditioning unit we refer to the operation
manual provided by the original equipment manufacturer.
The batteries of the infra-red remote control may only be replaced by batteries of the same
size and type as provided with the original product.
10.
Repair
Repairs to the AR-054 air conditioning unit may only be executed by applying original parts
that are assessed, converted and marked by Artidor. Repairs may only be carried out by
qualified skilled workers who have been trained in accordance with EN 60079-19. Applying of
non-assessed, non-converted, non-marked parts may lead to injury to persons and damage
to equipment.
Installation manual AR-054 window air conditioning system
E
12-2024
9 / 36