Technical specifications
Capacity
Connected power
Fuel
Capacity of fuel tank
Fuel consumption
Max. working pressure per tank
Air displacement
Motor capacity
Dimensions
Weight
Safety instructions
Above all: always ensure there is adequate ventilation. The heater uses oxygen. If this is not
supplied in sufficient measure, it will produce carbon monoxide. Inadequate ventilation
can therefore cause carbon monoxide poisoning and this can lead to serious illness or
death. Always ensure that the heater and the working area are supplied with continual
fresh air from outdoors. Make sure there are two 2,800 cm² (so 70 x 40 cm) openings to
the outside for every 100,000 Btu/hour: one low opening (close to the ground) and one
high opening (near the ceiling).
Fireball 37T: 1.26 x 2800 = 3528 cm² so: 2 openings of 40 x 90 cm.
The first signs of carbon monoxide poisoning are flu–like symptoms: headaches, dizziness,
burning eyes and nose, dry mouth and throat and nausea. If you are aware of these
symptoms, your heater may not be working correctly or there is inadequate ventilation.
You must ensure that fresh air is provided immediately! Have the heater checked and/or
ensure that there is adequate ventilation. One person may be more sensitive to carbon
monoxide than another. Pregnant women, people with heart or lung problems or
anaemia, the elderly and people under the influence of alcohol are at an increased risk.
Never use the heater in living-, work- or sleeping areas!
Know you heater: ensure that you (and any other heater users) understand the instruction
booklet and the labels on the heater. This will ensure you are aware of where it can be
used, its limitations and any potential hazards.
Never use the heater in a dangerous environment: not outdoors, where it is exposed to all
weather conditions, or in damp/wet/dusty locations. Do not use the heater in places
containing flammable or ignitable liquids or gases, e.g. fuels, paint, solvents, chemicals,
etc. This poses the risk of explosion! Moreover, keep your heater away from flammable
126.000 Btu/h
37 kW
31.800
220-240V~50Hz, 0,86 A
Paraffin or Diesel
32 l
3,6l/h
8 h
600 m³/h
210 W
890x405x510 mm
22,5 kg
34