Device informa-
For displaying the settings that will be of relevance to an energy supply company. The val-
tion
ues shown will depend on the country setup or the device-specific settings of the inverter.
Display area
General:
Country-specific set-
ting:
MPP Tracker:
Monitoring the grid:
Grid voltage limits:
Grid frequency limits:
Q-mode:
AC power limit:
AC voltage derating:
Fault Ride Through:
General / Country-specific setting / MPP tracker / Grid monitor-
ing / Grid voltage limits / Grid frequency limits / Q-mode / AC
power limit / AC voltage derating / Fault Ride Through
Device type
fam.
Setup - specified country setup
Version - version of country setup
Group - group for updating the inverter software
Tracker 1
Tracker 2
GMTi - start-up time of inverter in s
GMTr - reconnection time in s following a grid fault
ULL - mean grid voltage over 10 minutes in V.
LLTrip - trip time for long-term voltage monitoring
UILmax - upper inner grid voltage in V
UILmin -lower inner grid voltage in V
FILmax -upper inner grid frequency in Hz
FILmin - lower inner grid frequency in Hz
Current power factor setting cos phi
(e.g. Constant Cos(phi) / Constant Q / Q(U)-characteristic / etc.)
Max. P AC - manual power reduction
Status - ON / OFF voltage-dependent power reduction
GVDPRe - threshold from which the voltage-dependent power
reduction begins
GVDPRv - reduction gradient used to reduce the power, e.g.: 10
% per volt above the GVDPRe threshold.
Message - activates the sending of an info message via Fronius
Solar Net
Status - default setting: OFF
If the function is activated, the inverter does not switch off im-
mediately in the event of a short-term AC voltage interruption
(outside of the limits specified by the grid supplier), but instead
continues to feed in power for a defined period.
DB min - default setting: 90 %
"Dead Band Minimum" setting in percent
DB max - default setting: 120 %
"Dead Band Maximum" setting in percent
k-Fac. - default setting: 0