3.4 ELECTRICAL WIRING

WARNING
DO NOT EXCHANGE
NEUTRAL WITH PHASE
~
50Hz 230V
N
L
Limit thermostat
with manual
T
resetting

7 pin plug

N
L1
7 pole socket
Ignition
flame control
electrodes
552SE
D5336
S7072
2311
NOTES:
– Wires of 1 mm 2 section .
– The electrical wiring carried out by the installer must be in
– Connect 2nd stage thermostat between clamps T6 - T8
Switch with fuse
6A max.
Regulating thermostat
T
T1
S3
B4
T2
Brown
Blue
Brown
Blue
Black
White
Blue
Burner-earth
Fig. 11
To remove the control-box from the burner, loosen screw (A, Fig. 11) after
removing all components, the 7 pin plug and earth wire.
In case of disassembly of the flame control, retighten the screw (A)
with a torque wrench setting of 1 – 1.2 Nm.
A
compliance with the rules in force in the Country.
by removing the bridge.
TESTING: Check the shut-down of the burner by opening
the thermostats and the lock-out by darkening
the flame sensor.
st
1
stage
h
hour counter
(230V - 0.1A max.)
Remote lock-out lamp
(230V - 0.5A max.)

Flame sensor

nd
2
stage oil valve
2 1
5
GB
nd
2
stage hour counter
h
(230V - 0.1A max.)
n
nd
2
stage
T
thermostat
4 pin plug
T6
T7
T8
B5
4 pole socket
st
1
stage oil valve
M
~
3 2 1
M
ELECTRONIC
DELAYING DEVICE