MPP Tracker 1 / MPP Tracker 2
-
-
-
-
-
USB log book
Activates or deactivates the function for saving all error messages to a USB
flash drive
AUTO / OFF / ON
Input signal
-
SMS / relay
-
-
Isolation setting
-
-
TOTAL Reset
Under the LOG menu item, this setting resets the max. and min. voltage values
and the max. power of feeding in to zero.
Once the values have been reset, this action cannot be undone.
To reset the values to zero, press the 'Enter' key.
'CONFIRM' is displayed.
Press 'Enter' again.
The values are reset and the menu is displayed
46
MPP Tracker 2: ON / OFF (only for devices with multiple MPP trackers)
DC operating mode: MPP AUTO / FIX / MPP USER
-
MPP AUTO: normal operating status; the inverter automatically
searches for the ideal operating point
-
FIX: for entering a fixed DC voltage at which the inverter will operate
-
MPP USER: for entering a lower MP voltage above which the inverter
will search for its ideal operating point
Dynamic Peak Manager: ON / OFF
Fixed voltage: for inputting a fixed voltage (80–800 V)
MPPT start-up input voltage: for entering the start-up input voltage (80–
800 V)
Ext Sig. / S0-Meter / OFF operating mode
Ext Sig. operating mode:
-
Triggering
method: Warning (warning shown on display) / Ext. Stop
(inverter switches off)
-
Connection
type: N/C (normally closed contact) / N/O (normally open
contact)
S0 meter operating mode – see chapter
means of inverter
on page 16.
Grid feed-in limit
-
Field for entering the maximum grid feed-in power in W. If this value
is exceeded, the inverter regulates down to the set value within the
time required by national standards and regulations.
-
Pulses per kWh
Field for entering the pulses per kWh of the S0 meter.
Event delay:
for entering the time delay after which an SMS is sent or the relay is to
switch
900–86,400 seconds
Event counter:
for entering the number of events that lead to signalling:
10–255
Isolation warning: ON / OFF
Threshold warning: for entering a threshold that leads to a warning
Dynamic power reduction by