VACON · 136
9.1.2
NETSPANNING 380–500 V
Tabel 46: Nominaal vermogen van Vacon
Frame
Type
frequentier
egelaar
MR4
0003
0004
0005
0008
0009
0012
MR5
0016
0023
0031
MR6
0038
0046
0061
MR7
0072
0087
0105
MR8
0140
0170
0205
MR9
0261
0310
* = Zie hoofdstuk 9.1.5 Toelaatbare overbelasting.
9
®
100 FLOW bij netspanning 380–500 V, 50–60 Hz, 3~
Belastbaarheid*
Continustro
Ingangsstr
om I
L
[A]
oom I
in
[A]
3.4
3.4
4.8
4.6
5.6
5.4
8.0
8.1
9.6
9.3
12.0
11.3
16.0
15.4
23.0
21.3
31.0
28.4
38.0
36.7
46.0
43.6
61.0
58.2
72.0
67.5
87.0
85.3
105.0
100.6
140.0
139.4
170.0
166.5
205.0
199.6
261.0
258.0
310.0
303.0
TECHNISCHE GEGEVENS, VACON® 100 FLOW
10%
Maximumst
overbelasti
room I
S
2s
ngsstroom
[A]
3.7
5.2
5.3
6.8
6.2
8.6
8.8
11.2
10.6
16.0
13.2
19.2
17.6
24.0
25.3
32.0
34.1
46.0
41.8
62.0
50.6
76.0
67.1
92.0
79.2
122.0
95.7
144.0
115.5
174.0
154.0
210.0
187.0
280.0
225.5
340.0
287.1
410.0
341.0
502.0
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Motorasvermogen
Netspannin
Netspannin
g 400 V
g 480 V
10%
10%
overbelasti
overbelasti
ng 40 °C
ng 40 °C
[kW]
[pk]
1.1
1.5
1.5
2.0
2.2
3.0
3.0
4.0
4.0
5.0
5.5
7.5
7.5
10.0
11.0
15.0
15.0
20.0
18.5
25.0
22.0
30.0
30.0
40.0
37.0
50.0
45.0
60.0
55.0
75.0
75.0
100.0
90.0
125.0
110.0
150.0
132.0
200.0
160.0
250.0