Display text
|Relay operating
cycles|
|Max. run time 1
or
|Max. run occur 1
|Communication error|
|Alarm level|
Is a potential-free contact activated? If yes, which? (W = warning, E = error)
1
42 / 140
PFC
Possible cause
1
E
Maximum operating cycles
exceeded.
2|
E
Pump runs too long per pumping
operation.
2|
or
-
Pump runs too frequently within a
short time.
E
Telecontrol modem error
W
Level exceedance detected
Installation and operating manual
Remedial measure
Can be acknowledged. Inform cus-
tomer service. Error appears after a
further 1000 operating cycles.
Check the system design, inform the
customer service department if nec-
essary.
Check the system design, inform the
customer service department if nec-
essary.
No network/credits, no connection to
the modem, equipment fault
If it occurs frequently, check the
design and performance of the
pump(s).
532-010