* Volg bij het instellen van de parameters de volgende regels:
AC under-voltage level 1 protection value≥AC under-voltage level 2
protection value≥AC under-voltage level 3 protection value;
AC over-voltage level 1 protection value≤AC over-voltage level 2 protection
value≤AC over-voltage level 3 protection value;
AC under-frequency level 1 protection value≥AC under-frequency level 2
protection value≥AC under-frequency level 3 protection value;
AC over-frequency level 1 protection value≤AC over-frequency level 2
protection value≤AC over-frequency level 3 protection value;
AC under-voltage level 1 protection time≥AC under-voltage level 2 protection
time≥AC under-voltage level 3 protection time;
AC over-voltage level 1 protection time≥AC over-voltage level 2 protection
time≥AC over-voltage level 3 protection time;
AC under-frequency level 1 protection time≥AC under-frequency level 2
protection time≥AC under-frequency level 3 protection time;
AC over-frequency level 1 protection time≥AC over-frequency level 2
protection time≥AC over-frequency level 3 protection time;
AC under-voltage recovery value≥AC under-voltage level 1 protection
value + 3V;
AC over-voltage recovery value≤AC over-voltage level 1 protection
value - 3V;
AC under-frequency recovery value≥AC under-frequency level 1 protection
value + 0,01Hz;
AC over-frequency recovery value≤AC over-frequency level 1 protection
value - 0,01Hz.
LET OP
He bereik en de standaardwaarde in bovenstaande tabel dienen
uitsluitend ter referentie.
De veiligheidsparameters kunnen per land verschillen. Raadpleeg de
normen in elk land voor meer informatie.