Configuration
3.1.1
Gas concentration display in normal mode
Display on central unit:
LED shows steady green light
Press the
or
key.
Display A: the current
concentration at transmitter 1
is displayed.
Display M: the mean value of the
concentration is displayed.
The concentrations at other transmitters
connected to the system bus can be
queried by pressing the
or
again.
4
Configuration
To individually configure a device different to the factory default settings,
use a PC and the VarioControl software (see the Technical Handbook).
4.1
Factory default settings
On initial start up, the system operates with the basic factory settings:
The emergency power supply connection and the alkaline batteries
of the central unit are not monitored.
Mean values are calculated over a period of 15 minutes.
Alarm threshold settings for the different transmitters are according
to the table on Page 31.
30
Dräger VarioGard
Transmitter
1
20.9 % by vol. O2 I
Transmitter
2
18 ppm CO
I
keys