Download Print deze pagina

Daikin Tewis ECO2SMART Handleiding pagina 63

STORED APPLICATION PARAMETERS (TABLE 2.6)
LABEL
CP01_TipoRegulacionCPs_Asp
CP02_NumCPs_Asp
CP03_TipoCPVariable_Asp
CP05_SetPresion_Asp
CP06_BandaPresion_Asp
CP07_Banda_Presion_PID_Asp
CP08_Ti_PID_Asp
CP09_Td_PID_Asp
CP14_MinVel_Inverter_Asp
CP15_NumStepsErr_Asp
CP16_Vel_InverterErr_Asp
CP17_Off_Inverter_Asp
CP18_Inv_Min_Freq
CP19_Inv_Max_Freq
CP20_MaxIncInverter
CP21_MaxDecInverter
CP22_MaxPercPIDVariador
CP23_TMaxParadaCpsECO2
CP24_SetPresion_Asp_PC
CP25_Off_Inverter_PC
CP50_Tipo_Satur_CP1_Asp
CP51_Tipo_Satur_CP2_Asp
CP52_Tipo_Satur_CP3_Asp
CP53_Tipo_Satur_CP4_Asp
CP54_Etapas_CP1_Asp
CP55_Etapas_CP2_Asp
CP56_Etapas_CP3_Asp
CP57_Etapas_CP4_Asp
C/ Sir Alexander Fleming, 7 _ 46980 Paterna (Valencia) SPAIN info@tewis.com www.tewis.com (+34) 963 13 42 02
DESCRIPTION
CGF "REGULATION" COMPRESSORS
Regulation compressor type:
0 → Neutral Zone
1 → Proportional
Number of ECO2 compressors
ECO2 Inverter Exists
Set Compressor Suction Pressure
Compressor Suction Pressure Band
Compressor Suction Pressure PID Band
Compressor Suction Integral PID
Compressor Suction Derived PID
ECO2 Inverter minimum velocity
Number Steps in error sensor Suction
Inverter Velocity in error sensor Suction
Differential limit Off ECO2 Inverter
Minimum frequency inverter compressor
Maximum frequency inverter compressor
Maximum variation per second increase in
power Drive CPs
Maximum variation per second decrease
in power Drive CPs
Maximum variation per second CPs PID Drive CPs
Maximum time forced shut down ECO2 compressors
Pressure setting Compressors in PC mode
Pressure value inverter off in PC mode
CFG COMPRESSORS "TYPE"
CP1 Suction Saturation Type:
0 → Coil ON with increased power
1 → Coil OFF with increased power
CP2 Suction Saturation Type:
CP3 Suction Saturation Type:
CP4 Suction Saturation Type:
CP1 Suctions Number of stages
0 → Deactivated
1 → 1 Capacity
2 → 2 Capacity
3 → 3 Capacity
4 → 4 Capacity
CP2 Suction Number of stages
CP3 Suction Number of stages
CP4 Suction Number of stages
DEFAULT
UM
LEVEL
VALUE
0
Num
1
4
Num
1
1
Num
1
38.0
Bar
1
3.0
Bar
1
30.0
Bar
1
90.0
Sec
1
0
Sec
1
1.0
%
1
0
Num
1
0
%
1
22.0
bar
1
30
hz
1
70
hz
1
3.0
%
1
3.0
%
1
0
%
1
10
sec
1
40.0
bar
1
35.0
bar
1
0
Num
1
0
Num
1
0
Num
1
0
Num
1
0
Num
1
1
Num
1
1
Num
1
1
Num
1
19
loading

Deze handleiding is ook geschikt voor:

Tewis av0026.v6