• M2M2 of Backup Danfoss 782 Control Unit
(CN08_TypeCentralitaMT=2), (CN10_CentralBackup =1) and
(CN12_ModbusDanfoss =0)
»
Modbus RTU Address: 31
»
Ethernet Configuration:
*
*
*
• M2M2 of Main Danfoss 772 Control Unit (CN08_TipoCentralitaMT=3)
and (CN12_ModbusDanfoss =0)
»
Modbus RTU Address: 32
»
Ethernet Configuration:
*
*
*
• Backup Danfoss 772 Control Unit (CN08_TypeCentralitaMT =3),
(CN10_CentralBackup =1) and (CN12_ModbusDanfoss =0)
»
Modbus RTU Address: 33
»
Ethernet Configuration:
*
*
*
Below is a summary table of the addresses of the elements that can make up the system:
Interface
ECO2 RS485-2 19200 NONE
MASTER
TMS
19200 NONE
INTERNAL
19200 NONE
SUPERVISOR
Bus Config.
Interface
ECO2 RS485-2 19200 NONE
MASTER
TMS
19200 NONE
INTERNAL
19200 NONE
SUPERVISOR
Bus Config.
C/ Sir Alexander Fleming, 7 _ 46980 Paterna (Valencia) SPAIN info@tewis.com www.tewis.com (+34) 963 13 42 02
IP: 10.39.245.236
Default Gateway: 10.39.245.254
Mask: 255.255.255.0
IP: 10.39.245.237
Default Gateway: 10.39.245.254
Mask: 255.255.255.0
IP: 10.39.245.236
Default Gateway: 10.39.245.254
Mask: 255.255.255.0
ECO2
9000 PRO
RE 485-1
RE 485-1 RE 485-2 PLUGIN BMS-2
10/11
9
10/11
DANFOSS AKPC - 782 XVD ECO2
M2M2
32/33 (COM1 tSH)
32/33 (COM3 tSH)
SLAVE (TABLE 8)
CAREL pRACK
BMS-3 (card)
20/21 (COM1 tSH)
10/11
20/21 (COM3 tSH)
20/21
SLAVE (TABLE 8)
V910 ECO2
iEM3255
1
7
6
DANFOSS AKPC - 782
M2M2
30/31 (COM1 tSH)
30/31 (COM3 tSH)
XVD HP
XVD FG
XVD "X"
2/4
3/5
X
31