Parameter list
Line
Function, display
Block "Space heating"
en
61
Heating limit for
NORMAL heating
(ECO day)
62
Heating limit for
REDUCED heating
(ECO night)
63
Building time con-
stant
64
Quick setback
65
Room temperature
source
66
Type of optimization
67
Maximum heating-
up time
Building Technologies
Factory setting
Setting
Explanations, notes and tips
(Range)
17.0 °C
Setting --.- = function disabled
(--.- / −5.0...+25.0)
°C
...................
5.0 °C
Setting --.- = function disabled
(--.- / −5.0...+25.0)
°C
...................
20 h
Light = 10 h
(0...50)
h
Medium = 25 h
......................
Heavy = 50 h
1
0 = no quick setback
(0 / 1)
1 = quick setback
.........................
A
0 = no room temperature sen-
(0 / 1 / 2 / 3 / A)
.........................
1 = room unit at terminal A6
2 = room temperature sensor at
3 = mean value of the two units
A = automatic selection
0
0 = optimization with room
(0 / 1)
.........................
1 = optimization with room
(setting 0 only allows optimum
start control)
00:00 h
Maximum forward shift for
(00:00...42:00)
h
switching on before start of
......................
occupancy
Setting 00:00 = optimization of
switching on disabled
74 319 0620 0 a
sor present
terminal B5
at terminals A6 and B5
model
temperature sensor / room
unit
17.04.2008
28/152