68
Maximum optimum
shutdown
(0:00...6:00)
69
Maximum limitation
of room temperature
(--.- / 0...35)
70
Effect of room tem-
perature
71
Boost of room tem-
perature setpoint
with boost heating
72
Parallel shift of
heating curve
(−4.5...+4.5)
73
Type of heating
curve adjustment
Block "Three-position actuator for heating circuit"
81
Maximum limitation
of flow temperature
(--- / 0...140)
82
Minimum limitation
of flow temperature
(--- / 0...140)
83
Maximum increase
rate of flow tem-
(--- / 1...600)
perature
84
Excess temperature
mixing valve
85
Actuator running
time
Building Technologies
0:00 h
Maximum forward shift for
h
switching off before end of
......................
occupancy
setting 0:00 = optimization of
switching off disabled
--.- °C
Setting --.- = limitation disabled
°C
Only with room temperature
...................
sensor / room unit
4
Compensation factor for effect
(0...20)
of room temperature
.........................
Function possible only with
room unit / room temperature
sensor
5 °C
(0...20)
°C
...................
0.0 °C
Value in °C room temperature
°C
(remote setting via data bus)
...................
0
0 = analog adjustment
(0...2)
1 = digital adjustment on the
.........................
controller and via bus
2 = digital adjustment via bus
only
--- °C
Setting --- = function disabled
°C
(e.g. for floor heating 55 °C)
...................
--- °C
Setting --- = function disabled
°C
...................
--- °C/h
Setting --- = function disabled
°C/h
(function prevents cracking
..............
noise in piping)
10 °C
For use in interconnected plants
(0...50)
°C
(setpoint elevation for primary
...................
controller)
120 s
(30...873)
s
......................
74 319 0620 0 a
17.04.2008
en
29/152