174 Pump overrun time
175 Pump kick
176 Changeover winter-/
en
summertime
177 Changeover sum-
mer-/ wintertime
178 Clock operation
179 Bus supply
180 Outside tempera-
ture source
Block "Contact H2"
184 Function when
terminals H2–M are
linked
Building Technologies
6 min
(0...40)
min
................
0 = no periodic pump run
0
1 = weekly pump run active
(0 / 1)
.........................
Setting: Earliest possible
25.03
changeover time
(01.01 ... 31.12)
.........................
Setting: Earliest possible
25.10
changeover time
(01.01 ... 31.12)
.........................
0 = autonomous clock in the
0
(0...3)
.........................
1 = time from bus; clock (slave)
2 = time from bus; clock (slave)
3 = time from bus; central clock
0 = no bus supply through the
A
(0 / A)
.........................
A = bus supply through the
When from data bus:
A
Enter segment and device
(A / 00.01...14.16)
.........................
number of source, or
enter A, in which case the
source is automatically ascer-
tained
0
0 = heat demand signal to heat
(0 / 1)
.........................
1 = heat demand signal to
74 319 0620 0 a
controller
with no remote setting
with remote setting
(master)
controller
controller
source
heating circuit
17.04.2008